Inspection & Testing Schedule

How often portable fire extinguishers need attention, based on NFPA 10 (2022 edition).

What's needed and when

TaskHow oftenWho
Visual inspection: in place, gauge in the green, seal intact, no damage, nothing blocking itEvery monthBuilding owner or staff
Annual maintenance & certification: full inspection, new tag and sealEvery yearLicensed technician
6-year maintenance: internal inspection and refillEvery 6 yearsLicensed technician
Hydrostatic test: cylinder pressure testEvery 5 or 12 years (see below)Licensed technician
RechargeAfter any use, or when the gauge or inspection shows it's neededLicensed technician

By extinguisher type

Type6-year maintenanceHydrostatic test
Stored-pressure dry chemical (ABC, BC, Purple K)Every 6 yearsEvery 12 years
Halotron / clean agentEvery 6 yearsEvery 12 years
Carbon dioxide (CO2)Not requiredEvery 5 years
Water and water mistNot requiredEvery 5 years
Wet chemical (Class K)Not requiredEvery 5 years

Dates count from the last 6-year maintenance or hydro test (or the manufacture date for a unit that's never been serviced). We track these for you and list the next due dates on your extinguisher location list after every visit. Your local fire code or insurer may have additional requirements.